Air curtains
Accessory Installation
stat 80°C, operation thermostat 60°C) is forbidden.
It is forbidden to operate the electric heater without
the outlet air temperature control and without ensuring
a steady ow of transported air.
Checking during the First Air curtain Start-Up
During test operation, check the air curtain for unusual
noises (squeaking, resonance, etc.), excessive vibrati-
ons or the smell of burning insulation.
The testing operation must last at least 30 minutes.
After the test operation has nished, it is advisable to
inspect the air curtain unit again. If a failure occurs, the
air curtain must be stopped immediately and the failure
removed - for possible solutions, refer to the "Trouble-
shooting" section on page 24.
Controllers - Overview and Connection
Operation of the basic air curtain version without fan
output control and heating can be controlled by a co-
mmon wall switch (ON-OFF) connected to the LV+Q3
respectively LE+Q3E terminals. This switch is not inclu-
ded in the delivery.
To control air curtains equipped with a control (i.e. multi-
ple-stage fan control and/or external electric heater out-
put control), Siemens standard controllers, refer to page
14, or a similar controller can be used.
The controller selection depends on the air curtain type
and required control. For features and usage of particu-
lar controllers, refer to table 9 on page 20.
For specication of recommended conductors for co-
nnection of controllers, refer to table 10 on page 20.
Keep in mind that lower fan speeds (i.e. lower speed
stages) will reduce the air curtain efciency.
Figure 15 – thermostatic valve connection
Thermostatic Valve
A thermostatic valve, either a TVW-P 9 thermostatic re-
gulator (with a separate sensor and a capillary) or TVW-
-E (thermo-electric actuator enabling remote control),
can be installed on the upper necks of the water heat
exchanger of both C1 and D2 air curtains.
TVW-P and TVW-E Valve Installation Procedure
Verify that the water heater circuit is disconnected
from the media inlet piping.
Make sure the device is safely disconnected from
the power supply. When connecting the valve, observe
the instructions included in these Installation and Ope-
rating Instructions.
Connect the valve.
Remove the laminated side wall on the header side
(C1 air curtain) - 4 lock screws.
Pull the sensor with capillary through the grommet
situated in the upper air curtain panel.
Fix the sensor to the holder:
C1 air curtain: insert the sensor in the hole in
the
side wall and x the holder (see gure # 16).
D2 air curtain: pull the sensor with capillary
through the retainers on the upper supporting bar, and
x the sensor to the holder (see gure #17)..
Mount all removed curtains parts in reversed order.
Attention!
It is possible to place thermostatic valve with regulator
inside of air curtain. 2,5 m long air curtain has two wa-
ter exchangers which demands intallation of thermosta-
tic valves in 2 sets.
TVW-R Thermostatic Valve Installation Procedure
(to be installed in the inside of the D2 air curtain)
Verify that the water heater circuit is disconnected
from the media inlet piping.
Make sure the device is safely disconnected from
the power supply.
Remove the inlet panel (two locks).
Release and open the lower service panel.
Remove the closing G3/4" nut from the side water
heat exchanger inlet header neck, and screw it onto the
header upper neck.
Install the following components on the inlet header
neck in the following sequence: 90°elbow, 65mm long
3/4" extension, angle valve (without head). Observe the
instructions on page 11.
Screw the low G3/4" nut with O50/O28 washer onto
the 150mm long 3/4" extension, and connect the com-
plete assembly to the valve inlet side, refer to page 18.
Install the second low G3/4" nut and O50/ O28
washer assembly onto the 150mm extension upper inlet
neck, and tighten it against the upper panel (contra-tigh-
ten against the lower assembly).
Install the regulator (head) on the valve.
Pull the sensor with capillary through the retainers
on the upper supporting bar, and x the sensor to the
holder.
TVW-P or TVW-E
(optional accessory)
T-tting 3/4" (not included in the delivery)
Air-venting valve 1" (not included in the delivery)
Pipe union with double-end thread 1"
(not included in the delivery)
Elbow 90° (not included in the delivery)
Rubber grommet enabling the sensor insertion
(part of the product)